🏗 System Architecture
The AI Suite is built on a two-tier operational framework designed to automate client intake while maintaining strict engineering safety standards.
1. The Configurator Engine
- Target Rooms: Standard rectangular or square spaces.
- Logic: Automatically calculates structural air gaps (subtracting 10cm total width/depth) and matches user constraints against standard 57mm solid wood catalog models.
2. Spatial Planning Engine
- Target Rooms: Complex architecture involving attic roof slopes (Kniestock), niches, or wellness suites.
- Logic: Applies individual engineering evaluation rules and flags custom dimensioning for human engineering review.
🛡 Non-Negotiable Architect Safeguards (VETO Rules)
- The 5cm Air Gap Rule: Minimum 5cm ventilation gap required on all sides. Flush wall mounting is strictly forbidden.
- Door Clear Radius: Requires a minimum 100cm outward door swing clearance.
- Attic Clearance: Sauna heater must be located at peak height (min. 200cm). Any zone under 100cm ceiling height is classified as a forbidden zone.
- Glass Clearance: Minimum 15cm distance required between heater unit and structural glass panels.